Aquip were approached to assist a client with repairing an Autronica fire alarm system on a vehicle carrier vessel.

With the only trained Autronica AutroSafe 3 Service Engineer in Australia, our Perth team worked with the client to perform the repair.

Specifications

Project

Autronica Fire Alarm System Repair

Project Overview
  • A vehicle carrier vessel desperately needed the fire alarm system repaired. The vessel runs a legacy Fire Alarm System, the Autronica AutroSafe 3, which was superseded by AutroSafe 4.
  • The Aquip Perth team hold the only trained AutroSafe 3 Service Engineer in Australia.
  • Our Service Engineer made arrangements to fly over to Melbourne to carry-out the repair.
Project Challenges
  • We were informed that the Australian Maritime Safety Authority had refused permission for the vessel to leave Brisbane.
  • The vessel was taken to anchorage off Brisbane to await our Service Engineer’s arrival, where it later was brought into the port, ready and waiting for his arrival.
  • Once our Service Engineer flew to Brisbane and examined the vessel, he noticed that the system had lost some of its programming.
  • He worked to replace the EAC processor card with the spare, programmed the new card and initialised the system.
  • Two faults were present at the reboot stage but were related to a limit switch on a fire door magnetic switch and were fixed by adjustment.
Project Results
  • The system eventually appeared as fault-free and the Surveyor later jumped on board, where the system was tested again and approved.
  • The screen once again showed as fault-free – something we like to call the ‘Autronica Screen of Happiness.’